SPONSOR: |
Rep.
Mitchell & Sen. Ennis |
|
Reps. Bennett, Carson,
Mulrooney, Plant, Viola; Sens. Hall-Long, McDowell |
HOUSE OF REPRESENTATIVES 145th GENERAL ASSEMBLY |
HOUSE BILL NO. 376 |
AN ACT TO AMEND TITLE 16 OF THE DELAWARE CODE RELATING TO FIRE PREVENTION. |
Section 1. Amend §6603, Title 16 of the Delaware Code by adding a new subsection “(d)” thereto as follows:
“(d) The State Fire Prevention Commission shall promulgate regulations consistent with the following language:
(1)
Floor Proximity
Emergency Lighting - The State Fire Marshall shall require that emergency
lighting fixtures, wherever required by regulations promulgated pursuant to
this Chapter, be arranged to provide the required illumination automatically,
within five (5) seconds of interruption of normal lighting conditions due to
any of the following: failure of a public utility or other outside electrical
power supply; opening of a circuit breaker or fuse; manual acts including
accidental opening of a switch controlling normal lighting facilities; or
manual or automatic activation of a fire alarm system. Illumination shall be provided for not less
than 90 minutes. Such emergency lighting
fixtures shall be fully-recessed in the wall, within 36 inches of the finished
floor, to provide a visible delineation of the path of travel. Such emergency lighting fixtures shall be
UL924 listed and
(2)
Floor Proximity Exit Signs - The State Fire Marshall shall require that, in addition
to wherever exit signs are required by regulations promulgated pursuant to this
Chapter, exit access doors and exit doors be marked by floor proximity exit
signs. Such signs shall be located not
less than 6 nor more than 18 inches from the finished floor. Such signs shall be internally illuminated or
photoluminescent and shall illuminate automatically, within five (5) seconds of
interruption of normal lighting conditions due to any of the following: failure
of a public utility or other outside electrical power supply; opening of a
circuit breaker or fuse; manual acts including accidental opening of a switch
controlling normal lighting facilities; or manual or automatic activation of a
fire alarm system. Where internally
illuminated, signs shall be illuminated for a minimum of 60 minutes, shall read
EXIT, shall be UL924 listed or, where signs are photoluminescent, shall be
UL1994 or
SYNOPSIS
This Act updates Delaware’s Fire Prevention
Regulations to require installation of floor proximity emergency lighting and
floor proximity exit signs in all new buildings, occupancy conversions, mixed
occupancy buildings and additions and repairs to existing buildings. Floor Proximity Exit Signs shall be
installed in addition to exit signs currently required under |